Loads¶
Definition¶
The load element can be used to model consumption loads (with positive active power) as well as generation loads (with negative active power).
Connections¶
A load can be either star-connected or delta-connected depending on whether its phases include a neutral or not.
Star (wye) connection¶
Here is the diagram of a star-connected three-phase load:
In Roseau Load Flow, the phases argument of the constructor must contain "n" for star loads.
Note
You can create star connected constant-power or constant-impedance loads even on buses that don’t have a neutral. In this case, the load’s neutral will be floating and its potential can be accessed similar to normal star loads.
Delta connection¶
Here is the diagram of a delta-connected three-phase load:
In Roseau Load Flow, the phases argument of the constructor must not contain "n" for delta loads.
Available Results¶
The following results are available for all loads:
Result Accessor |
Default Unit |
Type |
Description |
|---|---|---|---|
|
\(V\) |
complex array |
The potentials of each phase of the load |
|
\(A\) |
complex array |
The line currents flowing into each phase of the load |
|
\(V\!A\) |
complex array |
The line powers flowing into each phase of the load |
|
\(V\) |
complex array |
The phase-to-neutral voltages if the load has a neutral, the phase-to-phase voltages otherwise |
|
\(A\) |
complex array |
The currents flowing in each component (dipole) of the load. |
|
\(V\!A\) |
complex array |
The powers dissipated by each component (dipole) of the load. |
Additionally, the following results are available for loads with a neutral:
Result Accessor |
Default Unit |
Type |
Description |
|---|---|---|---|
|
\(V\) |
complex array |
The phase-to-neutral voltages of the load |
And the following results are available for loads with more than one phase:
Result Accessor |
Default Unit |
Type |
Description |
|---|---|---|---|
|
\(V\) |
complex array |
The phase-to-phase voltages of the load |
And the following results are available for three-phase loads:
Result Accessor |
Default Unit |
Type |
Description |
|---|---|---|---|
|
\(\%\) |
number |
The voltage unbalance of the load according to the IEC, IEEE or NEMA definition |
|
\(\%\) |
number |
The Current Unbalance Factor (CUF) of the load |
Available models¶
The ZIP model is commonly used to represent electric loads in static grid analysis. This model considers the voltage dependency of loads. ZIP stands for the three load types:
Z = constant impedance load
I = constant current load
P = constant power load
The following load models are available in Roseau Load Flow:
API Reference¶
- class AbstractLoad(id: Id, bus: roseau.load_flow.models.buses.Bus, *, phases: str | None = None, connect_neutral: bool | None = None)
Bases:
roseau.load_flow.models.connectables.AbstractDisconnectable[_CyL_co],abc.ABCAn abstract class of an electric load.
- The subclasses of this class can be used to model:
star-connected loads using a phases constructor argument containing “n”
delta-connected loads using a phases constructor argument not containing “n”
AbstractLoad constructor.
- Parameters:
id – A unique ID of the load in the network loads.
bus – The bus to connect the load to.
phases – The phases of the load. A string like
"abc"or"an"etc. The bus phases are used by default. The order of the phases is important. For a full list of supported phases, see the class attributeallowed_phases. All phases of the load must be present in the phases of the connected bus. Multiphase loads are allowed to be connected to buses that don’t have a neutral ifconnect_neutralis not set toTrue.connect_neutral – Specifies whether the load’s neutral should be connected to the bus’s neutral or left floating. By default, the load’s neutral is connected when the bus has a neutral. If the bus does not have a neutral, the load’s neutral is left floating by default. To override the default behavior, pass an explicit
TrueorFalse.
- element_type: Final = 'load'
The type of the element. It is a string like
"load"or"line"etc.
- property res_inner_currents: Q_[ComplexArray]
The load flow result of the currents that flow in the inner components of the load (A).
- property res_inner_powers: Q_[ComplexArray]
The load flow result of the powers that flow in the inner components of the load (VA).
Unlike res_powers, the inner powers do not depend on the reference of potentials. They are the physical powers consumed by each of the load dipoles.
- classmethod from_dict(data: JsonDict, *, include_results: bool = True) AbstractLoad
Create an element from a dictionary created with
to_dict().Note
This method does not work on all classes that define it as some of them require additional information to be constructed. It can only be safely used on the ElectricNetwork, LineParameters and TransformerParameters classes.
- Parameters:
data – The dictionary containing the element’s data.
include_results – If True (default) and the results of the load flow are included in the dictionary, the results are also loaded into the element.
- Returns:
The constructed element.
- type: ClassVar[str]
- property is_disconnected: bool
Is this element disconnected from the network?
- disconnect() None
Disconnect this element from the network. It cannot be used afterwards.
- property bus: roseau.load_flow.models.buses.Bus
The bus of the element.
- property has_floating_neutral: bool
Does this element have a floating neutral?
- property res_currents: Q_[ComplexArray]
The load flow result of the element currents (A).
- property res_powers: Q_[ComplexArray]
The load flow result of the “line powers” flowing into the element (VA).
- res_current_unbalance() Q_[float]
Calculate the current unbalance (CU) on this element.
The calculation depends on the definition of current unbalance:
Current Unbalance Factor (CUF):
\(CUF = \dfrac{I_\mathrm{2}}{I_\mathrm{1}} \times 100 \, (\%)\)
Where \(I_{\mathrm{2}}\) is the magnitude of the negative-sequence (inverse) current and \(I_{\mathrm{1}}\) is the magnitude of the positive-sequence (direct) current.
- allowed_phases: Final
The allowed phases for a terminal element are:
P-P-P or P-P-P-N:
"abc","abcn"P-P or P-P-N:
"ab","bc","ca","abn","bcn","can"P-N:
"an","bn","cn"
- property phases: str
The phases of the element.
- property res_potentials: Q_[ComplexArray]
The load flow result of the element potentials (V).
- property res_voltages: Q_[ComplexArray]
The load flow result of the element voltages (V).
If the element has a neutral, the voltages are phase-to-neutral voltages for existing phases in the order
[Van, Vbn, Vcn]. If the element does not have a neutral, the voltages are phase-to-phase for existing phases in the order[Vab, Vbc, Vca].To always get phase-to-phase voltages, use the property
res_voltages_pp. To always get phase-to-neutral voltages, use the propertyres_voltages_pn.
- property res_voltages_pp: Q_[ComplexArray]
The load flow result of the element’s phase-to-phase voltages (V).
Raises an error if the element has only one phase.
- property res_voltages_pn: Q_[ComplexArray]
The load flow result of the element’s phase-to-neutral voltages (V).
Raises an error if the element does not have a neutral.
- res_voltage_unbalance(definition: Literal['VUF', 'LVUR', 'PVUR'] = 'VUF') Q_[float]
Calculate the voltage unbalance (VU) on this element.
- Parameters:
definition –
The definition of the voltage unbalance, one of the following:
VUF: The Voltage Unbalance Factor defined by the IEC (default). This is also called the “True Definition”.LVUR: The Line Voltage Unbalance Rate defined by NEMA.PVUR: The Phase Voltage Unbalance Rate defined by IEEE.
- Returns:
The voltage unbalance in percent.
The calculation depends on the definition of voltage unbalance:
Voltage Unbalance Factor (VUF):
\(VUF = \dfrac{V_\mathrm{2}}{V_\mathrm{1}} \times 100 \, (\%)\)
Where \(V_{\mathrm{2}}\) is the magnitude of the negative-sequence (inverse) voltage and \(V_{\mathrm{1}}\) is the magnitude of the positive-sequence (direct) voltage.
Line Voltage Unbalance Rate (LVUR):
\(LVUR = \dfrac{\Delta V_\mathrm{Line,Max}}{\Delta V_\mathrm{Line,Mean}} \times 100 (\%)\).
Where \(\Delta V_\mathrm{Line,Mean}\) is the arithmetic mean of the line voltages and \(\Delta V_\mathrm{Line,Max}\) is the maximum deviation between the measured line voltages and \(\Delta V_\mathrm{Line,Mean}\).
The Phase Voltage Unbalance Rate (PVUR):
\(PVUR = \dfrac{\Delta V_\mathrm{Phase,Max}}{\Delta V_\mathrm{Phase,Mean}} \times 100 (\%)\).
Where \(\Delta V_\mathrm{Phase,Mean}\) is the arithmetic mean of the phase voltages and \(\Delta V_\mathrm{Phase,Max}\) is the maximum deviation between the measured phase voltages and \(\Delta V_\mathrm{Phase,Mean}\).
- is_multi_phase: Final = True
Is the object multi-phase?
- property network: _N_co | None
Return the network the element belong to (if any).
- id
- classmethod from_json(path: StrPath, *, include_results: bool = True) Self
Construct an element from a JSON file created with
to_json().Note
This method does not work on all classes that define it as some of them require additional information to be constructed. It can only be safely used on the ElectricNetwork, LineParameters and TransformerParameters classes.
- Parameters:
path – The path to the network data file.
include_results – If True (default) and the results of the load flow are included in the file, the results are also loaded into the element.
- Returns:
The constructed element.
- to_dict(*, include_results: bool = True) JsonDict
Convert the element to a dictionary.
- Parameters:
include_results – If True (default), the results of the load flow are included in the dictionary. If no results are available, this option is ignored.
- Returns:
A JSON serializable dictionary with the element’s data.
- to_json(path: StrPath, *, include_results: bool = True) Path
Save this element to a JSON file.
Warning
If the file exists, it will be overwritten.
- Parameters:
path – The path to the output file to write the network to.
include_results – If True (default), the results of the load flow are included in the JSON file. If no results are available, this option is ignored.
- Returns:
The expanded and resolved path of the written file.
- results_to_dict(full: bool = False) JsonDict
Return the results of the element as a dictionary.
The results dictionary of an element contains the ID of the element, its phases, and the result. For example, bus.results_to_dict() returns a dictionary with the form:
{"id": "bus1", "phases": "an", "potentials": [[230.0, 0.0], [0.0, 0.0]]}
Note that complex values (like potentials in the example above) are stored as list of [real part, imaginary part] so that it is JSON-serializable
Using the full argument, bus.results_to_dict(full=True) leads to the following results:
{"id": "bus1", "phases": "an", "potentials": [[230.0, 0.0], [0.0, 0.0]], "voltages": [[230.0, 0.0]]}
The results dictionary of the network contains the results of all of its elements grouped by the element type. It has the form:
{ "buses": [bus1_dict, bus2_dict, ...], "lines": [line1_dict, line2_dict, ...], "transformers": [transformer1_dict, transformer2_dict, ...], "switches": [switch1_dict, switch2_dict, ...], "loads": [load1_dict, load2_dict, ...], "sources": [source1_dict, source2_dict, ...], "grounds": [ground1_dict, ground2_dict, ...], "potential_refs": [p_ref1_dict, p_ref2_dict, ...], }
where each dict is produced by the element’s results_to_dict() method.
- Parameters:
full – If True, all the results are added in the resulting dictionary. False by default.
- Returns:
The dictionary of results.
- results_to_json(path: StrPath, *, full: bool = False) Path
Write the results of the load flow to a json file.
Warning
If the file exists, it will be overwritten.
- Parameters:
path – The path to the output file to write the results to.
full – If True, all the results are added in the resulting dictionary, including results computed from other results (such as voltages that could be computed from potentials). False by default.
- Returns:
The expanded and resolved path of the written file.
- class ImpedanceLoad(id: Id, bus: roseau.load_flow.models.buses.Bus, *, impedances: ComplexScalarOrArrayLike1D, phases: str | None = None, connect_neutral: bool | None = None)
Bases:
AbstractLoad[roseau.load_flow_engine.cy_engine.CyAdmittanceLoad | roseau.load_flow_engine.cy_engine.CyDeltaAdmittanceLoad]A constant impedance load.
ImpedanceLoad constructor.
- Parameters:
id – A unique ID of the load in the network loads.
bus – The bus to connect the load to.
impedances –
A single impedance value or an array-like of impedance values for each phase component. Either complex values (Ohms) or a
Quantityof complex values.When a scalar value is provided, it creates a balanced load with the same impedance for each phase. To create an unbalanced load, provide a vector of impedance values with the same length as the number of components of the load.
phases – The phases of the load. A string like
"abc"or"an"etc. The bus phases are used by default. The order of the phases is important. For a full list of supported phases, see the class attributeallowed_phases. All phases of the load must be present in the phases of the connected bus. Multiphase loads are allowed to be connected to buses that don’t have a neutral ifconnect_neutralis not set toTrue.connect_neutral – Specifies whether the load’s neutral should be connected to the bus’s neutral or left floating. By default, the load’s neutral is connected when the bus has a neutral. If the bus does not have a neutral, the load’s neutral is left floating by default. To override the default behavior, pass an explicit
TrueorFalse.
- type: Final = 'impedance'
- property impedances: Q_[ComplexArray]
The impedances of the load (Ohms).
- class CurrentLoad(id: Id, bus: roseau.load_flow.models.buses.Bus, *, currents: ComplexScalarOrArrayLike1D, phases: str | None = None)
Bases:
AbstractLoad[roseau.load_flow_engine.cy_engine.CyCurrentLoad | roseau.load_flow_engine.cy_engine.CyDeltaCurrentLoad]A constant current load.
CurrentLoad constructor.
- Parameters:
id – A unique ID of the load in the network loads.
bus – The bus to connect the load to.
currents –
A single current value or an array-like of current values for each phase component. Either complex values (A) or a
Quantityof complex values. The complex currents provided define the currents magnitudes and their phase shift from the voltages of the load. For example, a current of10*exp(-90°j)represents an inductive constant current of 10 A.When a scalar value is provided, it creates a balanced load with the same current for each phase. To create an unbalanced load, provide a vector of current values with the same length as the number of components of the load.
phases – The phases of the load. A string like
"abc"or"an"etc. The bus phases are used by default. The order of the phases is important. For a full list of supported phases, see the class attributeallowed_phases. All phases of the load must be present in the phases of the connected bus.
- type: Final = 'current'
- property currents: Q_[ComplexArray]
The currents of the load (Amps).
Setting the currents will update the load’s currents and invalidate the network results.
- class PowerLoad(id: Id, bus: roseau.load_flow.models.buses.Bus, *, powers: ComplexScalarOrArrayLike1D, phases: str | None = None, flexible_params: roseau.load_flow.models.flexible_parameters.FlexibleParameter | Iterable[roseau.load_flow.models.flexible_parameters.FlexibleParameter] | None = None, connect_neutral: bool | None = None)
Bases:
AbstractLoad[roseau.load_flow_engine.cy_engine.CyPowerLoad | roseau.load_flow_engine.cy_engine.CyDeltaPowerLoad | roseau.load_flow_engine.cy_engine.CyFlexibleLoad | roseau.load_flow_engine.cy_engine.CyDeltaFlexibleLoad]A constant power load.
PowerLoad constructor.
- Parameters:
id – A unique ID of the load in the network loads.
bus – The bus to connect the load to.
powers –
A single power value or an array-like of power values for each phase component. Either complex values (VA) or a
Quantityof complex values.When a scalar value is provided, it creates a balanced load with the same power for each phase. The scalar value passed is assumed to be the power of each component of the load, not the total multi-phase power. To create an unbalanced load, provide a vector of power values with the same length as the number of components of the load.
phases – The phases of the load. A string like
"abc"or"an"etc. The bus phases are used by default. The order of the phases is important. For a full list of supported phases, see the class attributeallowed_phases. All phases of the load must be present in the phases of the connected bus. Multiphase loads are allowed to be connected to buses that don’t have a neutral ifconnect_neutralis not set toTrue.flexible_params –
A
FlexibleParametersobject to make the load flexible, i.e., controllable based on the voltage using the commonly known P(U) and Q(U) controls. These parameters are used to compute the flexible powers of the load which could be different from the input powers.It is also possible to pass an iterable of
FlexibleParameterobjects to create unbalanced control settings, one for each phase of the load.connect_neutral – Specifies whether the load’s neutral should be connected to the bus’s neutral or left floating. By default, the load’s neutral is connected when the bus has a neutral. If the bus does not have a neutral, the load’s neutral is left floating by default. To override the default behavior, pass an explicit
TrueorFalse.
- type: Final = 'power'
- property powers: Q_[ComplexArray]
The powers of the load (VA).
Setting the powers will update the load’s power values and invalidate the network results.
- property flexible_params: list[roseau.load_flow.models.flexible_parameters.FlexibleParameter] | None
The flexible parameters of the load or None if the load is not flexible.
If the load is flexible, this property returns a list of
FlexibleParameterobjects that define the control settings of each phase of the load.
- property is_flexible: bool
- property res_flexible_powers: Q_[ComplexArray]
The load flow result of the load flexible powers (VA).
This property is only available for flexible loads.
It returns the “inner powers” of the load instead of the “line powers” flowing into the load connection points. This property is equivalent to the
res_inner_powersproperty, not to theres_powersproperty. Prefer usingres_inner_powersbecause it is available for all loads.